Diamond Dotted Paper For Distribution Transformer
In accordance with GB/T5591.3.1-2008
-
COLORnatural color/customized
-
FREE SAMPLEA4;A3
-
THERMAL CLASSA 105℃
-
AVAILABLE WIDTH1000mm/customized
-
THICKNESS0.076-0.50mm
-
Diamond Dotted Paper For Distribution Transformer
In accordance with GB/T5591.3.1-2008
Description: DDP is produced by coating modified epoxy-resin in diamond-dotted patterns on electrical insulating paper.
Advantage: In the process of coil desiccation, the coated epoxy-resin would be melted in a certain temperature and become adhesive. With the temperature increased, the melted resin would cure to C-stage, and firmly adhere each adjoining layer of the coil, thus forming a winding section. If a short circuit occurs in the coil, the resin bond strength would sufficiently prevent the displacement of each winding layer, which ensures the long-term mechanical and physical properties of the insulation structure. As the resin coating distributes in a diamond-dotted pattern, little quantity of the resin would soak into the insulating paper during the melting and curing process, which ensures the elimination of air content in the insulating paper and guarantees the soakage of oil, minimizing the damages of corona and partial discharge.
Applications: it is suitable for turn-to-turn insulation of coil wires on oil-immersed power transformers and suitable for layer insulation of coils on distribution transformers.
ITEM
Property
Unit
Index
1
Thickness and Tolerance
mm
0.08
±0.005
0.13
±0.007
0.15±0.01
0.18
±
0.01
0.20±0.01
0.25
±0.01
0.30
±0.01
0.35
±0.02
0.38
±0.02
0.45±
0.02
0.50±
0.03
2
Density
g/cm³
0.85~1.10
3
One Side Coating
µm
6~12
10~15
4
Moisture Content
%
4.0~8.0
5
Ash Content
%
≤1.0
6
Water Extraction of Electrical Conductivity
mS/m
≤10
7
PH Water Extract
6.5~8.5
8
Oil Absorption
%
≥20
9
Bond Strength
Kpa
≥650
10
Tensile Strength
TD
N/10mm
60
110
160
180
230
≥250
MD
30
50
70
80
100
≥120
11
BDV
KV
0.88
1.37
2.00
2.10
2.25
≥2.50
﹥﹥1 DDP Technical Data
﹥﹥2 Curing conduction stock
2.1 Curing: 90℃±2 ℃/3h firstly , then130℃±5℃/6h, or according customer needs
2.2 Storage: ≤40℃, dry, clean in warehouse. Avoid fire, heat and sunlight.
2.3 Storage life: 12 months. Still effective if qualified in retest after 12 months.
-